CO₂ is electrically nonconductive and noncorrosive. After a CO₂ Fire Suppression System has been discharged, no residue is left behind and no cleanup is required.

CO₂ Fire Suppression Systems can be designed and installed in both local application and total flooding configurations, or a combination of the two.

In a local application system, CO₂ is discharged directly onto a specific hazard or protected area within a larger space. In contrast, a total flooding system distributes CO₂ throughout the entire enclosed room or space to achieve the required fire suppression concentration.

  • fire-defense-co2-free-standing-rack-systems-under-fabrication
  • fire-defense-co2-total-flooding-small-enclosed-chamber-linear-heat-detection2
  • fire-defense-co2-local-application-industrial-equipment
  • fire-defense-co2-total-flooding-cylinder-bank-marine-engine-room
  • fire-defense-co2-emergency-manual-actuation-warning-signage


While highly effective at extinguishing fires, CO₂ Fire Suppression Systems are generally not considered safe for use in normally occupied areas.

However, with careful hazard evaluation and the implementation of appropriate safeguards (including engineered safety features and personnel training) there are scenarios where CO₂ systems can be safely utilized in occupied spaces.

Discharge testing of two combination CO₂ Fire Suppression Systems following installation, verifying proper local application and total flooding operation.

Get a Design + Installation Quote →

Get an Inspection + Testing + Maintenance Quote →

Note: NFPA makes its codes and standards available online for free. Select View Free Access under Current & Prior Editions and create a free account.

Visit NFPA 12: Carbon Dioxide Extinguishing Systems →

  • fire-defense-co2-manual-release-station-on-preassembled-system
  • fire-defense-co2-cylinder-recharge-mechanical-pressure-gauge
  • fire-defense-co2-high-pressure-main-and-reserve-cylinder-inspection-tags.webp

Questions & Answers

Personnel working in or around protected areas should receive training on system operation, alarm recognition, evacuation procedures, lockout controls, and emergency response protocols. This training ensures that individuals understand the life safety risks associated with CO₂ discharge, the required precautions prior to system maintenance, and the proper actions to take in the event of a system discharge.

High-pressure systems store CO₂ in cylinders at approximately 850 psi at room temperature and are commonly used for most industrial applications. Low-pressure systems store CO₂ in refrigerated bulk tanks at lower pressure (approximately 300 psi) and are typically used for larger hazards requiring significant agent quantities.

NFPA 12 does not permit manual abort switches on CO₂ Fire Suppression Systems. In order to suppress a fire, CO₂ systems are designed to quickly achieve a potentially life-threatening concentration of CO₂ gas. A manual abort function could create hesitation, encourage occupants to remain in the protected space, or prevent the system from achieving its required design concentration. The life safety strategy is immediate evacuation rather than giving occupants a perceived option to delay system discharge.